Bushing insulators are designed to provide electrical connections between circuits through the chambers of an enclosure or partition while ensuring electrical insulation. Bushing insulators are used in electric motors, pumps, transformers, switchgear, and electrical equipment. Bushing insulators consist of copper through-pins positioned along the axis of a brass sleeve with a thrust flange, effectively electrically insulated by insulating materials placed between them.

I M2 Ex db eb I Mb

II 2G Ex db eb IIC Gb

 

Ask for the product

Insulation bushing type T:

Rated voltage: 3700V to 11kV

Rated current: up to 800A

Working temperature: -40oC to +120oC

Relative humidity of air [40°C]: 95%

Corrosivity category C5 according to PN-EN ISO 12944-2

I M2 Ex db eb I Mb; II 2G Ex db eb IIC Gb

PN-EN IEC 60079-0:2018, equivalent to IEC 60079-0:2017; PN-EN 60079-1:2014, equivalent to IEC 60079-1:2014; PN-EN 60079-7:2016, equivalent to IEC 60079-1:2015

Parameters of T..-M42(C40)G.. insulators

Insulator type 

M1 

M2 

Mw 

Current-carrying capacity [A] 

T10-M42(C40)G.. 

M10 

M10 

- 

200 

T12-M42(C40)G.. 

M12 

M12 

- 

315 

T20-M(C).. 

M16 

M16 

- 

630 

T10/12-M42(C40)G.. 

M10 

M12 

- 

200 

T10/16-M42(C40)G.. 

M10 

M16 

- 

315 

T12/16-M42(C40)G.. 

M12 

M16 

- 

450 

T12/10-M42(C40)G.. 

M12 

M10 

- 

200 

T16/10-M42(C40)G.. 

M16 

M10 

- 

315 

T16/12-M42(C40)G.. 

M16 

M12 

- 

450 

T12/10z-M42(C40)G.. 

M12 

- 

M10 

315 

T12/12z-M42(C40)G.. 

M12 

- 

M12 

315 

T16/12z-M42(C40)G.. 

M16 

- 

M12 

630 

T12/10w-M42(C40)G. 

- 

M12 

M10 

315 

T12/12w-M42(C40)G. 

- 

M12 

M12 

315 

T26/12w-M42(C40)G. 

- 

M16 

M12 

630 

Tw10-M42(C40)G.. 

- 

- 

M10 

450 

Tw12-M42(C40)G.. 

- 

- 

M12 

630 

Parameters of T..-M(C)(60, 70)(N, P, R)..-(D) insulator

Insulator type 

M1 

M2 

Mw 

Current-carrying capacity.[A] 

T10-M(C)(60,70)(N,P,R).. 

M10 

M10 

- 

200 

T12-M(C)(60,70)(N,P,R).. 

M12 

M12 

- 

315 

T16-M(C)(60,70)(N,P,R).. 

M16 

M16 

- 

630 

T20-M(C)(60,70)(N,P,R).. 

M20 

M20 

- 

630 

T10/12-M(C)(60,70)(N,P,R)... 

M10 

M12 

- 

200 

T10/16-M(C)(60,70)(N,P,R).. 

M10 

M16 

- 

315 

T12/10-M(C)(60,70)(N,P,R).. 

M12 

M10 

- 

200 

T12/16-M(C)(60,70)(N,P,R).. 

M12 

M16 

- 

450 

T12/20-M(C)(60,70)(N,P,R).. 

M12 

M20 

- 

450 

T16/10-M(C)(60,70)(N,P,R).. 

M16 

M10 

- 

315 

T16/12-M(C)(60,70)(N,P,R).. 

M16 

M12 

- 

450 

T16/20-M(C)(60,70)(N,P,R).. 

M16 

M20 

- 

630 

T20/12-M(C)(60,70)(N,P,R).. 

M20 

M12 

- 

450 

T20/16-M(C)(60,70)(N,P,R).. 

M20 

M16 

- 

630 

T12/10z-M(C)(60,70)(N,P,R).. 

M12 

- 

M10 

315 

T12/12z-M(C)(60,70)(N,P,R).. 

M12 

- 

M12 

315 

T16/12z-M(C)(60,70)(N,P,R).. 

M16 

- 

M12 

630 

T20/12z-M(C)(60,70)(N,P,R).. 

M20 

- 

M12 

630 

T12/10w-M(C)(60,70)(N,P,R).. 

- 

M12 

M10 

315 

T12/12w-M(C)(60,70)(N,P,R).. 

- 

M12 

M12 

315 

T16/12w-M(C)(60,70)(N,P,R).. 

- 

M16 

M12 

630 

T20/12w-M(C)(60,70)(N,P,R).. 

- 

M20 

M12 

630 

Tw10-M(C)(60,70)(N,P,R).. 

- 

- 

M10 

450 

Tw12-M(C)(60,70)(N,P,R).. 

- 

- 

M12 

630 

Tw16-M(C)(60,70)(N,P,R).. 

- 

- 

M16 

800 

Remarks: 
N: 7200V of rated voltage 
P: 10000V of rated voltage 
R:11000V of rated voltage 

Parameters of  T..-M(C)80(N, P, R)(A, B, C).. insulator

Insulator type 

M1 

M2 

Mw 

Current-carrying capacity [A] 

T10-M(C)80.. 

M10 

M10 

- 

200 

T12-M(C)80.. 

M12 

M12 

- 

315 

T16-M(C)80.. 

M16 

M16 

- 

630 

T20-M(C)80.. 

M20 

M20 

- 

630 

T12/10z-M(C)80.. 

M12 

- 

M10 

200 

T12/12z-M(C)80.. 

M12 

- 

M12 

315 

T16/12z-M(C)80.. 

M16 

- 

M12 

630 

T20/12z-M(C)80.. 

M20 

- 

M12 

630 

T12/10w-M(C)80.. 

- 

M12 

M10 

200 

T12/12w-M(C)80.. 

- 

M12 

M12 

315 

T16/12w-M(C)80.. 

- 

M16 

M12 

630 

T20/12w-M(C)80.. 

- 

M20 

M12 

630 

Tw12-M(C)80.. 

- 

- 

M12 

630 

Remarks: 
N: 7200V of rated voltage 
P: 10000V of rated voltage 
R:11000V of rated voltage 

Parameters of T..(d)-M(C)110.. insulators (11000 V)

Insulator type 

M1 

M2 

M3 

M4 

Current-carrying capacity [A] 

T12-M(C)110.. 

M12 

M12 

- 

- 

315 

T16-M(C)110.. 

M16 

M16 

- 

- 

450 

T20-M(C)110.. 

M20 

M20 

- 

- 

630 

T12/16-M(C)110.. 

M12 

M16 

- 

- 

315 

T16/12-M(C)110.. 

M16 

M12 

- 

- 

315 

T16/20-M(C)110.. 

M16 

M20 

- 

- 

450 

T20/16-M(C)110.. 

M20 

M16 

- 

- 

450 

T12/12z-M(C)110.. 

M12 

- 

M12 

- 

315 

T12/16z-M(C)110.. 

M12 

- 

M16 

- 

315 

T12/20z-M(C)110.. 

M12 

- 

M20 

- 

315 

T16/12z-M(C)110.. 

M16 

- 

M12 

- 

315 

T16/16z-M(C)110.. 

M16 

- 

M16 

- 

450 

T16/20z-M(C)110.. 

M16 

- 

M20 

- 

450 

T20/12z-M(C)110.. 

M20 

- 

M12 

- 

315 

T20/16z-M(C)110.. 

M20 

- 

M16 

- 

450 

T20/20z-M(C)110.. 

M20 

- 

M20 

- 

630 

T12/12w-M(C)110.. 

- 

M12 

- 

M12 

315 

T12/16w-M(C)110.. 

- 

M12 

- 

M16 

315 

T12/20w-M(C)110.. 

- 

M12 

- 

M20 

315 

T16/12w-M(C)110.. 

- 

M16 

- 

M12 

315 

T16/16w-M(C)110.. 

- 

M16 

- 

M16 

450 

T16/20w-M(C)110.. 

- 

M16 

- 

M20 

450 

T20/12w-M(C)110.. 

- 

M20 

- 

M12 

315 

T20/16w-M(C)110.. 

- 

M20 

- 

M16 

450 

T20/20w-M(C)110.. 

- 

M20 

- 

M20 

630 

T12d-M(C)110.. 

M12 

- 

- 

- 

315 

T16d-M(C)110.. 

M16 

- 

- 

- 

450 

T20d-M(C)110.. 

M20 

- 

- 

- 

630 

Tw12-M(C)110.. 

- 

- 

M12 

M12 

630A 

Tw12/16-M(C)110.. 

- 

- 

M12 

M16 

630 

Tw16/12-M(C)110.. 

- 

- 

M16 

M12 

630 

Tw16-M(C)110.. 

- 

- 

M16 

M16 

630 

Tw12d-M(C)110.. 

- 

- 

- 

M12 

315 

Tw16d-M(C)110.. 

- 

- 

- 

M16 

450 

Parameters of T..x..-M(C)116(D, N, P, R).. insulators

Insulator type 

M1 

M2 

Mw 

Current-carrying capacity [A] 

T10x(3,4)-M(C)116(D,N,P,R).. 

M10 

M10 

- 

(3 lub 4)x210 

T12x(3,4)-M(C)116(D,N,P,R).. 

M12 

M12 

- 

(3 lub 4)x250 

T16x3-M(C)116(D,N,P,R).. 

M16 

M16 

- 

3x400 

T10/12x(3,4)-M(C)116(D,N,P,R).. 

M10 

M12 

- 

(3 lub 4)x210 

T10/16x3-M(C)116(D,N,P,R).. 

M10 

M16 

- 

3x250 

T12/16x3-M(C)116(D,N,P,R).. 

M12 

M16 

- 

3x400 

T12/10x(3,4)-M(C)116(D,N,P,R).. 

M12 

M10 

- 

(3 lub 4)x210 

T16/10x3-M(C)116(D,N,P,R).. 

M16 

M10 

- 

3x250 

T16/12x3-M(C)116(D,N,P,R).. 

M16 

M12 

- 

3x400 

T12/10x(3,4)z-M(C)116(D,N,P,R).. 

M12 

- 

M10 

(3 lub 4)x250 

T12/12x(3,4)z-M(C)116(D,N,P,R).. 

M12 

- 

M12 

(3 lub 4)x315 

T16/12x3z-M(C)116(D,N,P,R).. 

M16 

- 

M12 

3x400 

T12/10x(3,4)w-M(C)116(D,N,P,R).. 

- 

M12 

M10 

(3 lub 4)x250 

T12/12x(3,4)w-M(C)116(D,N,P,R).. 

- 

M12 

M12 

(3 lub 4)x315 

T16/12x3w-M(C)116(D,N,P,R).. 

- 

M16 

M12 

3x400 

Tw10x(3,4)-M(C)116(D,N,P,R).. 

- 

- 

M10 

(3 lub 4)x250 

Tw12x(3,4)-M(C)116(D,N,P,R).. 

- 

- 

M12 

(3 lub 4)x400 

Rated voltage 
D: 2000V  
N: 8000V 
P: 10000V 
R: 11000V 

in