- New
Cable glands are electrical devices that are used to protect electrical cables in explosion-prone areas. These glands contain special materials that prevent the spread of sparks and electrical arcs, which could cause an explosion. Cable inlets for hazardous areas are mainly used in the chemical, refining, petroleum and other industries where there is a risk of explosion due to the presence of flammable gases, liquids or dust.
Explosion protection:
I M2 Ex db I Mb
I M2 Ex eb I Mb
II 1D Ex tb IIIC Da
Ask for the product
Cable glands type W1(2)d...(S), W1(2)du..(S) and W3d.. are intended for the introduction of power cables and wires into the fireproof casing of electrical equipment used in underground and surface mining plants in areas at risk of methane and/or coal dust explosion (group I devices) and in other places exposed to the risk of explosive atmospheres of gases (group II devices).
|
Application:
|
Ex installations above and below earth, equipment group I & II
|
|
Design:
|
robust, with flange, heavy duty strain-relief clamp
|
|
Flange design:
|
with 4 mounting holes and O-ring
|
|
Sizes:
|
40 to 100
|
|
Sealing range:
|
ø 13 – 74 mm
|
|
Protection class:
|
IP55 (W1(2)d..)/IP65 (W1(2)d..u; W3d..)
|
|
Ambient temperature:
|
-40 °C to +40 °C
|
|
Operating temperature:
|
-40 °C to +90 °C
|
|
Material cable gland:
|
cast steel, for the other materials – ask for availability
|
|
Material sealing:
|
CMP
|
|
Surface treatment:
|
Special painting
|
|
Humidity:
|
100% with 35°C
|
|
Dust: |
≤1000mg/m3
|
|
Corrosion resistance:
|
CI-5 (PN-EN ISO 12944-2) |
|
Explosion protection:
|
I M2 Ex db I Mb
I M2 Ex eb I Mb II 1D Ex tb IIIC Da
|
|
Certificates:
|
ATEX, IECEx (for some models)
|
|
Standards:
|
PN-EN IEC 60079-0:2018-09, equivalent to EN IEC 60079-0:2018
PN-EN 60079-1:2014-12, equivalent to EN 60079-1:2014
PN-EN 60079-7:2016-02+A1:2018-03, equivalent to EN 60079-7:2015
PN-EN 60079-31:2014-10, equivalent to EN 60079-31:2014
|